Chapter 9 Roof Assemblies

About this chapter: Chapter 9 addresses the design and construction of roof assemblies. A roof assembly includes the roof deck, substrate or thermal barrier, insulation, vapor retarder and roof covering. This chapter provides the requirement for wind resistance of roof coverings. The types of roof covering materials and installation addressed by Chapter 9 are: asphalt shingles, clay and concrete tile, metal roof shingles, mineral-surfaced roll roofing, slate and slate-type shingles, wood shakes and shingles, built-up roofs, metal roof panels, modified bitumen roofing, thermoset and thermoplastic single-ply roofing, sprayed polyurethane foam roofing, liquid applied coatings and photovoltaic shingles. Chapter 9 also provides requirements for roof drainage, flashing, above-deck thermal insulation, rooftop-mounted photovoltaic systems and recovering or replacing an existing roof covering.

Section R901 General

R901.1 Scope

The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies.

Section R902 Fire Classification

R902.1 Roofing Covering Materials

Roofs shall be covered with materials as set forth in Sections R904 and R905. Class A, B or C roofing shall be installed in jurisdictions designated by law as requiring their use or where the edge of the roof is less than 3 feet (914 mm) from a lot line. Class A, B and C roofing required by this section to be listed shall be tested in accordance with UL 790 or ASTM E108.

Exceptions:
  1. Class A roof assemblies include those with coverings of brick, masonry and exposed concreteroof deck.
  2. Class A roof assemblies include ferrous or copper shingles or sheets, metal sheets and shingles, clay or concrete roof tile, or slate installed on noncombustible decks.
  3. Class A roof assemblies include minimum 16 ounces per square foot copper sheets installed over combustible decks.
  4. Class A roof assemblies include slate installed over underlayment over combustible decks.

R902.2 Fire-Retardant-Treated Shingles and Shakes

Fire-retardant-treated wood shakes and shingles shall be treated by impregnation with chemicals by the full-cell vacuum-pressure process, in accordance with AWPA C1. Each bundle shall be marked to identify the manufactured unit and the manufacturer, and shall be labeled to identify the classification of the material in accordance with the testing required in Section R902.1, the treating company and the quality control agency.

R902.3 Building-Integrated Photovoltaic Product

Building-integrated photovoltaic products installed as the roof covering shall be tested, listed and labeled for fire classification in accordance with Section R902.1.

R902.4 Rooftop-Mounted Photovoltaic Panel Systems

Rooftop-mounted photovoltaic panel systems installed on or above the roof covering shall be tested, listed and identified with a fire classification in accordance with UL 1703 and UL 2703. Class A, B or C photovoltaic panel systems and modules shall be installed in jurisdictions designated by law as requiring their use or where the edge of the roof is less than 3 feet (914 mm) from a lot line.

Section R903 Weather Protection

R903.1 General

Roof decks shall be covered with approved roof coverings secured to the building or structure in accordance with the provisions of this chapter. Roof assemblies shall be designed and installed in accordance with this code and the approved manufacturer's instructions such that the roof assembly shall serve to protect the building or structure.

R903.2 Flashing

Flashings shall be installed in a manner that prevents moisture from entering the wall and roof through joints in copings, through moisture permeable materials and at intersections with parapet walls and other penetrations through the roof plane.

R903.2.1 Locations

Flashings shall be installed at wall and roof intersections, wherever there is a change in roof slope or direction and around roof openings. A flashing shall be installed to divert the water away from where the eave of a sloped roof intersects a vertical sidewall. Where flashing is of metal, the metal shall be corrosion resistant with a thickness of not less than 0.019 inch (0.5 mm) (No. 26 galvanized sheet).

R903.2.2 Crickets and Saddles

A cricket or saddle shall be installed on the ridge side of any chimney or penetration more than 30 inches (762 mm) wide as measured perpendicular to the slope. Cricket or saddle coverings shall be sheet metal or of the same material as the roof covering.

Exception: Unit skylights installed in accordance with Section R308.6 and flashed in accordance with the manufacturer's instructions shall be permitted to be installed without a cricket or saddle.

R903.3 Coping

Parapet walls shall be properly coped with noncombustible, weatherproof materials of a width not less than the thickness of the parapet wall.

R903.4 Roof Drainage

Unless roofs are sloped to drain over roof edges, roof drains shall be installed at each low point of the roof.

R903.4.1 Secondary (Emergency Overflow) Drains or Scuppers

Where roof drains are required, secondary emergency overflow roof drains or scuppers shall be provided where the roof perimeter construction extends above the roof in such a manner that water will be entrapped if the primary drains allow buildup for any reason. Overflow drains having the same size as the roof drains shall be installed with the inlet flow line located 2 inches (51 mm) above the low point of the roof, or overflow scuppers having three times the size of the roof drains and having a minimum opening height of 4 inches (102 mm) shall be installed in the adjacent parapet walls with the inlet flow located 2 inches (51 mm) above the low point of the roof served. The installation and sizing of overflow drains, leaders and conductors shall comply with Sections 1106 and 1108 of the International Plumbing Code, as applicable.

Overflow drains shall discharge to an approved location and shall not be connected to roof drain lines.

Section R904 Materials

R904.1 Scope

The requirements set forth in this section shall apply to the application of roof covering materials specified herein. Roof assemblies shall be applied in accordance with this chapter and the manufacturer's installation instructions. Installation of roof assemblies shall comply with the applicable provisions of Section R905.

R904.2 Compatibility of Materials

Roof assemblies shall be of materials that are compatible with each other and with the building or structure to which the materials are applied.

R904.3 Material Specifications and Physical Characteristics

Roof covering materials shall conform to the applicable standards listed in this chapter.

R904.4 Product Identification

Roof covering materials shall be delivered in packages bearing the manufacturer's identifying marks and approved testing agency labels required. Bulk shipments of materials shall be accompanied by the same information issued in the form of a certificate or on a bill of lading by the manufacturer.

Section R905 Requirements for Roof Coverings

R905.1 Roof Covering Application

Roof coverings shall be applied in accordance with the applicable provisions of this section and the manufacturer's installation instructions. Unless otherwise specified in this section, roof coverings shall be installed to resist the component and cladding loads specified in Table R301.2(2), adjusted for height and exposure in accordance with Table R301.2(3).

R905.1.1 Underlayment

Underlayment for asphalt shingles, clay and concrete tile, metal roof shingles, mineral-surfaced roll roofing, slate and slate-type shingles, wood shingles, wood shakes, metal roof panels and photovoltaic shingles shall conform to the applicable standards listed in this chapter. Underlayment materials required to comply with ASTM D226, D1970, D4869 and D6757 shall bear a label indicating compliance to the standard designation and, if applicable, type classification indicated in Table R905.1.1(1). Underlayment shall be applied in accordance with Table R905.1.1(2). Underlayment shall be attached in accordance with Table R905.1.1(3).

  1. As an alternative, self-adhering polymer-modified bitumen underlayment complying with ASTM D1970 installed in accordance with both the underlayment manufacturer's and roof covering manufacturer's instructions for the deck material, roof ventilation configuration and climate exposure for the roof covering to be installed, shall be permitted.
  2. As an alternative, a minimum 4-inch-wide (102 mm) strip of self-adhering polymer-modified bitumen membrane complying with ASTM D1970, installed in accordance with the manufacturer's installation instructions for the deck material, shall be applied over all joints in the roof decking. An approvedunderlayment for the applicable roof covering for maximum ultimate design wind speeds, Vult, less than 140 miles per hour shall be applied over the entire roof over the 4-inch-wide (102 mm) membrane strips.
  3. As an alternative, two layers of underlayment complying with ASTM D226 Type II or ASTM D4869 Type III or Type IV shall be permitted to be installed as follows in 3.1—3.4:
    1. Apply a 19-inch-wide (483 mm) strip of underlayment parallel with the eave. Starting at the eave, apply 36-inch-wide (914 mm) strips of underlayment felt, overlapping successive sheets 19 inches (483 mm). End laps shall be 4 inches (102 mm) and shall be offset by 6 feet (1829 mm).
    2. The underlayment shall be attached with corrosion-resistant fasteners in a grid pattern of 12 inches (305 mm) between side laps with a 6-inch (152 mm) spacing at side and end laps.
    3. Underlayment shall be attached using metal or plastic cap nails with a nominal cap diameter of not less than 1 inch (25 mm). Metal caps shall have a thickness of not less than 32-gage sheet metal. Power-driven metal caps shall have a thickness of not less than 0.010 inch (0.25 mm). Minimum thickness of the outside edge of plastic caps shall be 0.035 inch (0.89 mm).
    4. The cap nail shank shall be not less than 0.083 inch (2.11 mm) for ring shank cap nails and 0.091 inch (2.31 mm) for smooth shank cap nails. Cap nail shank shall have a length sufficient to penetrate through the roof sheathing or not less than 3 /4 inch (19 mm) into the roof sheathing.
    TABLE R905.1.1(1)
    UNDERLAYMENT TYPES
    ROOF COVERING SECTION MAXIMUM ULTIMATE DESIGN WIND SPEED, Vult < 140 MPH
    MAXIMUM ULTIMATE DESIGN WIND SPEED, Vult ≥ 140 MPH
    Asphalt shingles R905.2 ASTM D226 Type I
    ASTM D4869 Type I, II, III or IV ASTM D6757 ASTM D4869 Type III or Type IV ASTM D6757 ASTM D2626 Type I ASTM D6380 Class M mineral-surfaced roll roofing ASTM D2626 Type I ASTM D6380 Class M mineral-surfaced roll roofing ASTM D4869 Type I, II, III or IV ASTM D4869 Type III or Type IV ASTM D4869 Type I, II, III or IV ASTM D4869 Type III or Type IV ASTM D4869 Type I, II, III or IV ASTM D4869 Type III or Type IV ASTM D4869 Type I, II, III or IV ASTM D4869 Type III or Type IV ASTM D4869 Type I, II, III or IV ASTM D4869 Type III or Type IV ASTM D4869 Type III or Type IV ASTM D6757 ASTM D6757 For SI: 1 mile per hour = 0.447 m/s.

    TABLE R905.1.1(2)
    UNDERLAYMENT APPLICATION
    ROOF COVERING SECTION MAXIMUM ULTIMATE DESIGN
    WIND SPEED, Vult < 140 MPH
    MAXIMUM ULTIMATE DESIGN
    WIND SPEED, Vult ≥ 140 MPH
    Asphalt shingles R905.2 For roof slopes from two units vertical in 12 units horizontal (2:12), up to four units vertical in 12 units horizontal (4:12), underlayment shall be two layers applied in the following manner: apply a 19-inch strip of underlayment felt parallel to and starting at the eaves. Starting at the eave, apply 36-inch-wide sheets of underlayment, overlapping successive sheets 19 inches. Distortions in the underlayment shall not interfere with the ability of the shingles to seal. End laps shall be 4 inches and shall be offset by 6 feet.

    For roof slopes of four units vertical in 12 units horizontal (4:12) or greater, underlayment shall be one layer applied in the following manner: underlayment shall be applied shingle fashion, parallel to and starting from the eave and lapped 2 inches, Distortions in the underlayment shall not interfere with the ability of the shingles to seal. End laps shall be 4 inches and shall be offset by 6 feet.

    For roof slopes of four units vertical in 12 units horizontal (4:12) or greater, underlayment shall be not fewer than one layer of underlayment felt applied shingle fashion, parallel to and starting from the eaves and lapped 2 inches. End laps shall be 4 inches and shall be offset by 6 feet.

    For roof slopes of four units vertical in 12 units horizontal (4:12) or greater, underlayment shall be one layer applied in the following manner: underlayment shall be applied shingle fashion, parallel to and starting from the eave and lapped 4 inches. End laps shall be 4 inches and shall be offset by 6 feet.

    For roof slopes of four units vertical in 12 units horizontal (4:12) or greater, underlayment shall be one layer applied in the following manner: underlayment shall be applied shingle fashion, parallel to and starting from the eave and lapped 2 inches. Distortions in the underlayment shall not interfere with the ability of the shingles to seal. End laps shall be 4 inches and shall be offset by 6 feet.

    For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s.

    The underlayment shall be attached with corrosion-resistant fasteners in a grid pattern of 12 inches between side laps with a 6-inch spacing at side and end laps.

    Underlayment shall be attached using metal or plastic cap nails or cap staples with a nominal cap diameter of not less than 1 inch. Metal caps shall have a thickness of not less than 32-gage sheet metal. Power-driven metal caps shall have a minimum thickness of 0.010 inch. Minimum thickness of the outside edge of plastic caps shall be 0.035 inch. The cap nail shank shall be not less than 0.083 inch for ring shank cap nails and 0.091 inch for smooth shank cap nails. Staples shall be not less than 21 gage. Cap nail shank and cap staple legs shall have a length sufficient to penetrate through the roof sheathing or not less than 3 /4 inch into the roof sheathing.

    The underlayment shall be attached with corrosion-resistant fasteners in a grid pattern of 12 inches between side laps with a 6-inch spacing at side and end laps.

    Underlayment shall be attached using metal or plastic cap nails or cap staples with a nominal cap diameter of not less than 1 inch. Metal caps shall have a thickness of not less than 32-gage sheet metal. Power-driven metal caps shall have a minimum thickness of 0.010 inch. Minimum thickness of the outside edge of plastic caps shall be 0.035 inch. The cap nail shank shall be not less than 0.083 inch for ring shank cap nails and 0.091 inch for smooth shank cap nails. Staples shall be not less than 21 gage. Cap nail shank and cap staple legs shall have a length sufficient to penetrate through the roof sheathing or not less than 3 /4 inch into the roof sheathing.

    For SI: 1 inch = 25.4 mm, 1 mile per hour = 0.447 m/s.

    R905.1.2 Ice Barriers

    In areas where there has been a history of ice forming along the eaves causing a backup of water as designated in Table R301.2(1), an ice barrier shall be installed for asphalt shingles, metal roof shingles, mineral-surfaced roll roofing, slate and slate-type shingles, wood shingles and wood shakes. The ice barrier shall consist of not fewer than two layers of underlayment cemented together, or a self-adhering polymer-modified bitumen sheet shall be used in place of normal underlayment and extend from the lowest edges of all roof surfaces to a point not less than 24 inches (610 mm) inside the exterior wall line of the building. On roofs with slope equal to or greater than eight units vertical in 12 units horizontal (67-percent slope), the ice barrier shall also be applied not less than 36 inches (914 mm) measured along the roof slope from the eave edge of the building.

    Exception: Detached accessory structures not containing conditioned floor area.

    R905.2 Asphalt Shingles

    The installation of asphalt shingles shall comply with the provisions of this section.

    R905.2.1 Sheathing Requirements

    Asphalt shingles shall be fastened to solidly sheathed decks.

    R905.2.2 Slope

    Asphalt shingles shall be used only on roof slopes of two units vertical in 12 units horizontal (17-percent slope) or greater. For roof slopes from two units vertical in 12 units horizontal (17-percent slope) up to four units vertical in 12 units horizontal (33-percent slope), double underlayment application is required in accordance with Section R905.1.1.

    R905.2.3 Underlayment

    Underlayment shall comply with Section R905.1.1.

    R905.2.4 Asphalt Shingles

    Asphalt shingles shall comply with ASTM D3462.

    R905.2.4.1 Wind Resistance of Asphalt Shingles

    Asphalt shingles shall be tested in accordance with ASTM D7158. Asphalt shingles shall meet the classification requirements of Table R905.2.4.1 for the appropriate ultimate design wind speed. Asphalt shingle packaging shall bear a label to indicate compliance with ASTM D7158 and the required classification in Table R905.2.4.1.

    Exception: Asphalt shingles not included in the scope of ASTM D7158 shall be tested and labeled in accordance with ASTM D3161. Asphalt shingle packaging shall bear a label to indicate compliance with ASTM D3161 and the required classification in Table R905.2.4.1.

    TABLE R905.2.4.1 CLASSIFICATION OF ASPHALT ROOF SHINGLES
    MAXIMUM ULTIMATE DESIGN WIND SPEED, Vult FROM FIGURE R301.2(5)A (mph)
    MAXIMUM BASIC WIND SPEED, VASD FROM TABLE R301.2.1.3
    (mph)
    ASTM D7158 a SHINGLE CLASSIFICATION
    ASTM D3161 SHINGLE CLASSIFICATION
    110 85 D, G or H A, D or F
    116 90 D, G or H A, D or F
    129 100 G or H A, D or F
    142 110 G or H F
    155 120 G or H F
    168 130 H F
    181 140 H F
    194 150 H F
    For SI: 1 foot = 304.8 mm; 1 mile per hour = 0.447 m/s.
    1. The standard calculations contained in ASTM D7158 assume Exposure Category B or C and a building height of 60 feet or less. Additional calculations are required for conditions outside of these assumptions.

    R905.2.5 Fasteners

    Fasteners for asphalt shingles shall be galvanized steel, stainless steel, aluminum or copper roofing nails, minimum 12-gage [0.105 inch (3 mm)] shank with a minimum 3 /8-inch-diameter (9.5 mm) head, complying with ASTM F1667, of a length to penetrate through the roofing materials and not less than 3 /4 inch (19.1 mm) into the roof sheathing. Where the roof sheathing is less than 3 /4 inch (19.1 mm) thick, the fasteners shall penetrate through the sheathing.

    R905.2.6 Attachment

    Asphalt shingles shall have the minimum number of fasteners required by the manufacturer's approved installation instructions, but not less than four fasteners per strip shingle or two fasteners per individual shingle. Where the roof slope exceeds 21 units vertical in 12 units horizontal (21:12, 175-percent slope), shingles shall be installed in accordance with the manufacturer's approved installation instructions.

    R905.2.7 Ice Barrier

    Where required, ice barriers shall comply with Section R905.1.2.

    R905.2.8 Flashing

    Flashing for asphalt shingles shall comply with this section and the asphalt shingle manufacturer's approved installation instructions.

    R905.2.8.1 Base and Cap Flashing

    Base and cap flashing shall be installed in accordance with manufacturer's instructions. Base flashing shall be of either corrosion-resistant metal of minimum nominal 0.019-inch (0.5 mm) thickness or mineral-surfaced roll roofing weighing not less than 77 pounds per 100 square feet (4 kg/m 2 ). Cap flashing shall be corrosion-resistant metal of minimum nominal 0.019-inch (0.5 mm) thickness.

    R905.2.8.2 Valleys

    1. For open valleys (valley lining exposed) lined with metal, the valley lining shall be not less than 24 inches (610 mm) wide and of any of the corrosion-resistant metals in Table R905.2.8.2.
    2. For open valleys, valley lining of two plies of mineral-surfaced roll roofing, complying with ASTM D3909 or ASTM D6380 Class M, shall be permitted. The bottom layer shall be 18 inches (457 mm) and the top layer not less than 36 inches (914 mm) wide.
    3. For closed valleys (valley covered with shingles), valley lining of one ply of smooth roll roofing complying with ASTM D6380 and not less than 36 inches wide (914 mm) or valley lining as described in Item 1 or 2 shall be permitted. Self-adhering polymer-modified bitumen underlayment complying with ASTM D1970 shall be permitted in lieu of the lining material.
    TABLE R905.2.8.2
    VALLEY LINING MATERIAL
    MATERIALMINIMUM THICKNESS
    (inches)
    GAGEWEIGHT
    (pounds)
    Cold-rolled copper0.0216 nominalASTM B370, 16 oz. per square foot
    Lead-coated copper0.0216 nominalASTM B101, 16 oz. per square foot
    High-yield copper0.0162 nominalASTM B370, 12 oz. per square foot
    Lead-coated high-yield copper0.0162 nominalASTM B101, 12 oz. per square foot
    Aluminum0.024
    Stainless steel28
    Galvanized steel0.017926 (zinc coated G90)
    Zinc alloy0.027
    Lead2 1 /2
    Painted terne20
    For SI: 1 inch = 25.4 mm, 1 pound = 0.454 kg.

    R905.2.8.3 Sidewall Flashing

    Base flashing against a vertical sidewall shall be continuous or step flashing and shall be not less than 4 inches (102 mm) in height and 4 inches (102 mm) in width and shall direct water away from the vertical sidewall onto the roof or into the gutter. Where siding is provided on the vertical sidewall, the vertical leg of the flashing shall be continuous under the siding. Where anchored masonry veneer is provided on the vertical sidewall, the base flashing shall be provided in accordance with this section and counterflashing shall be provided in accordance with Section R703.8.2.2. Where exterior plaster or adhered masonry veneer is provided on the vertical sidewall, the base flashing shall be provided in accordance with this section and Section R703.6.3.

    R905.2.8.4 Other Flashing

    Flashing against a vertical front wall, as well as soil stack, vent pipe and chimney flashing, shall be applied in accordance with the asphalt shingle manufacturer's printed instructions.

    R905.2.8.5 Drip Edge

    A drip edge shall be provided at eaves and rake edges of shingle roofs. Adjacent segments of drip edge shall be overlapped not less than 2 inches (51 mm). Drip edges shall extend not less than 1 /4 inch (6.4 mm) below the roof sheathing and extend up back onto the roof deck not less than 2 inches (51 mm). Drip edges shall be mechanically fastened to the roof deck at not more than 12 inches (305 mm) o.c. with fasteners as specified in Section R905.2.5. Underlayment shall be installed over the drip edge along eaves and under the drip edge along rake edges.

    R905.3 Clay and Concrete Tile

    The installation of clay and concrete tile shall comply with the provisions of this section.

    R905.3.1 Deck Requirements

    Concrete and clay tile shall be installed only over solid sheathing or spaced structural sheathing boards.

    R905.3.2 Deck Slope

    Clay and concrete roof tile shall be installed on roof slopes of two and one-half units vertical in 12 units horizontal (25-percent slope) or greater. For roof slopes from two and one-half units vertical in 12 units horizontal (25-percent slope) to four units vertical in 12 units horizontal (33-percent slope), double underlayment application is required in accordance with Section R905.3.3.

    R905.3.3 Underlayment

    Underlayment shall comply with Section R905.1.1.

    R905.3.4 Clay Tile

    Clay roof tile shall comply with ASTM C1167.

    R905.3.5 Concrete Tile

    Concrete roof tile shall comply with ASTM C1492.

    R905.3.6 Fasteners

    Nails shall be corrosion resistant and not less than 11-gage, 5 /16-inch (11 mm) head, and of sufficient length to penetrate the deck not less than 3 /4 inch (19 mm) or through the thickness of the deck, whichever is less. Attaching wire for clay or concrete tile shall not be smaller than 0.083 inch (2 mm). Perimeter fastening areas include three tile courses but not less than 36 inches (914 mm) from either side of hips or ridges and edges of eaves and gable rakes.

    R905.3.7 Application

    Tile shall be applied in accordance with this chapter and the manufacturer's installation instructions, based on the following:

    1. Climatic conditions.
    2. Roof slope.
    3. Underlayment system.
    4. Type of tile being installed.

    Clay and concrete roof tiles shall be fastened in accordance with this section and the manufacturer's installation instructions. Perimeter tiles shall be fastened with not less than one fastener per tile. Tiles with installed weight less than 9 pounds per square foot (0.4 kg/m 2 ) require not less than one fastener per tile regardless of roof slope. Clay and concrete roof tile attachment shall be in accordance with the manufacturer's installation instructions where applied in areas where the ultimate design wind speed exceeds 130 miles per hour (58 m/s) and on buildings where the roof is located more than 40 feet (12 192 mm) above grade. In areas subject to snow, not less than two fasteners per tile are required. In other areas, clay and concrete roof tiles shall be attached in accordance with Table R905.3.7.

    TABLE R905.3.7 CLAY AND CONCRETE TILE ATTACHMENT
    SHEATHING ROOF SLOPE NUMBER OF FASTENERS
    Solid without battens All One per tile
    Spaced or solid with battens and slope < 5:12Fasteners not required
    Spaced sheathing without battens 5:12 ≤ slope < 12:12One per tile/every other row
    12:12 ≤ slope < 24:12One per tile

    R905.3.8 Flashing

    At the juncture of roof vertical surfaces, flashing and counterflashing shall be provided in accordance with this chapter and the manufacturer's installation instructions and, where of metal, shall be not less than 0.019 inch (0.5 mm) (No. 26 galvanized sheet gage) corrosion-resistant metal. The valley flashing shall extend not less than 11 inches (279 mm) from the centerline each way and have a splash diverter rib not less than 1 inch (25 mm) in height at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (102 mm). For roof slopes of three units vertical in 12 units horizontal (25-percent slope) and greater, valley flashing shall have a 36-inch-wide (914 mm) underlayment of one layer of Type I underlayment running the full length of the valley, in addition to other required underlayment . In areas where the average daily temperature in January is 25°F (-4°C) or less, metal valley flashing underlayment shall be solid-cemented to the roofing underlayment for slopes less than seven units vertical in 12 units horizontal (58-percent slope) or be of self-adhering polymer-modified bitumen sheet.

    R905.4 Metal Roof Shingles

    The installation of metal roof shingles shall comply with the provisions of this section.

    R905.4.1 Deck Requirements

    Metal roof shingles shall be applied to a solid or closely fitted deck, except where the roof covering is specifically designed to be applied to spaced sheathing.

    R905.4.2 Deck Slope

    Metal roof shingles shall not be installed on roof slopes below three units vertical in 12 units horizontal (25-percent slope).

    R905.4.3 Underlayment

    Underlayment shall comply with Section R905.1.1.

    R905.4.3.1 Ice Barrier

    Where required, ice barriers shall comply with Section R905.1.2.

    R905.4.4 Material Standards

    Metal roof shingle roof coverings shall comply with Table R905.10.3(1). The materials used for metal roof shingle roof coverings shall be naturally corrosion resistant or be made corrosion resistant in accordance with the standards and minimum thicknesses listed in Table R905.10.3(2).

    R905.4.5 Application

    Metal roof shingles shall be secured to the roof in accordance with this chapter and the approved manufacturer's installation instructions.

    R905.4.6 Flashing

    Roof valley flashing shall be of corrosion-resistant metal of the same material as the roof covering or shall comply with the standards in Table R905.10.3(1). The valley flashing shall extend not less than 8 inches (203 mm) from the centerline each way and shall have a splash diverter rib not less than 3 /4 inch (19 mm) in height at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (102 mm). The metal valley flashing shall have a 36-inch-wide (914 mm) underlayment directly under it consisting of one layer of underlayment running the full length of the valley, in addition to underlayment required for metal roof shingles. In areas where the average daily temperature in January is 25°F (-4°C) or less, the metal valley flashing underlayment shall be solid-cemented to the roofing underlayment for roof slopes under seven units vertical in 12 units horizontal (58-percent slope) or self-adhering polymer-modified bitumen sheet.

    R905.5 Mineral-Surfaced Roll Roofing

    The installation of mineral-surfaced roll roofing shall comply with this section.

    R905.5.1 Deck Requirements

    Mineral-surfaced roll roofing shall be fastened to solidly sheathed roofs.

    R905.5.2 Deck Slope

    Mineral-surfaced roll roofing shall not be applied on roof slopes below one unit vertical in 12 units horizontal (8-percent slope).

    R905.5.3 Underlayment

    Underlayment shall comply with Section R905.1.1.

    R905.5.3.1 Ice Barrier

    Where required, ice barriers shall comply with Section R905.1.2.

    R905.5.4 Material Standards

    Mineral-surfaced roll roofing shall conform to ASTM D3909 or ASTM D6380, Class M.

    R905.5.5 Application

    Mineral-surfaced roll roofing shall be installed in accordance with this chapter and the manufacturer's instructions.

    R905.6 Slate Shingles

    The installation of slate shingles shall comply with the provisions of this section.

    R905.6.1 Deck Requirements

    Slate shingles shall be fastened to solidly sheathed roofs.

    R905.6.2 Deck Slope

    Slate shingles shall be used only on slopes of four units vertical in 12 units horizontal (33-percent slope) or greater.

    R905.6.3 Underlayment

    Underlayment shall comply with Section R905.1.1.

    R905.6.3.1 Ice Barrier

    Where required, ice barriers shall comply with Section R905.1.2.

    R905.6.4 Material Standards

    Slate shingles shall comply with ASTM C406.

    R905.6.5 Application

    Minimum headlap for slate shingles shall be in accordance with Table R905.6.5. Slate shingles shall be secured to the roof with two fasteners per slate. Slate shingles shall be installed in accordance with this chapter and the manufacturer's instructions.

    SLATE SHINGLE HEADLAP
    SLOPEHEADLAP (inches)
    4:12 ≤ slope < 8:124
    8:12 ≤ slope < 20:123
    Slope ≥ 20:122
    For SI: 1 inch = 25.4 mm.

    R905.6.6 Flashing

    Flashing and counterflashing shall be made with sheet metal. Valley flashing shall be not less than 15 inches (381 mm) wide. Valley and flashing metal shall be a minimum uncoated thickness of 0.0179-inch (0.5 mm) zinc coated G90. Chimneys, stucco or brick walls shall have not less than two plies of felt for a cap flashing consisting of a 4-inch-wide (102 mm) strip of felt set in plastic cement and extending 1 inch (25 mm) above the first felt and a top coating of plastic cement. The felt shall extend 2 inches (51 mm) over the base flashing.

    R905.7 Wood Shingles

    The installation of wood shingles shall comply with the provisions of this section.

    R905.7.1 Deck Requirements

    Wood shingles shall be installed on solid or spaced sheathing. Where spaced sheathing is used, sheathing boards shall be not less than 1-inch by 4-inch (25 mm by 102 mm) nominal dimensions and shall be spaced on centers equal to the weather exposure to coincide with the placement of fasteners.

    R905.7.1.1 Solid Sheathing Required

    In areas where the average daily temperature in January is 25°F (-4°C) or less, solid sheathing is required on that portion of the roof requiring the application of an ice barrier.

    R905.7.2 Deck Slope

    Wood shingles shall be installed on slopes of three units vertical in 12 units horizontal (25-percent slope) or greater.

    R905.7.3 Underlayment

    Underlayment shall comply with Section R905.1.1.

    R905.7.3.1 Ice Barrier

    Where required, ice barriers shall comply with Section R905.1.2.

    R905.7.4 Material Standards

    Wood shingles shall be of naturally durable wood and comply with the requirements of Table R905.7.4. WOOD SHINGLE MATERIAL REQUIREMENTS
    MATERIALMINIMUM GRADESAPPLICABLE
    GRADING RULES
    Wood shingles of

    R905.7.5 Application

    Wood shingles shall be installed in accordance with this chapter and the manufacturer's instructions. Wood shingles shall be laid with a side lap not less than 1 1 /2 inches (38 mm) between joints in courses, and two joints shall not be in direct alignment in any three adjacent courses. Spacing between shingles shall be not less than 1 /4 inch to 3 /8 inch (6.4 mm to 9.5 mm). Weather exposure for wood shingles shall not exceed those set in Table R905.7.5(1). Fasteners for untreated (naturally durable) wood shingles shall be box nails in accordance with Table R905.7.5(2). Nails shall be stainless steel Type 304 or 316 or hot-dipped galvanized with a coating weight of ASTM A153 Class D (1.0 oz/ft 2 ). Alternatively, two 16-gage stainless steel Type 304 or 316 staples with crown widths 7 /16 inch (11.1 mm) minimum, 3 /4 inch (19.1 mm) maximum, shall be used. Fasteners installed within 15 miles (24 km) of saltwater coastal areas shall be stainless steel Type 316. Fasteners for fire-retardant-treated shingles in accordance with Section R902 or pressure-impregnated-preservative-treated shingles of naturally durable wood in accordance with AWPA U1 shall be stainless steel Type 316. Fasteners shall have a minimum penetration into the sheathing of 3 /4 inch (19.1 mm). For sheathing less than 3 /4 inch in (19.1 mm) thickness, each fastener shall penetrate through the sheathing. Wood shingles shall be attached to the roof with two fasteners per shingle, positioned in accordance with the manufacturer's installation instructions. Fastener packaging shall bear a label indicating the appropriate grade material or coating weight.

    WOOD SHINGLE WEATHER EXPOSURE AND ROOF SLOPE
    ROOFING MATERIAL
    LENGTH (inches)
    GRADE EXPOSURE (inches)
    3:12 pitch to < 4:12
    4:12 pitch or steeper
    Shingles of naturally durable wood 16 No. 1 3 3 /4 5
    No. 2 3 1 /2 4
    No. 3 3 3 1 /2
    18 No. 1 4 1 /4 5 1 /2
    No. 2 4 4 1 /2
    No. 3 3 1 /2 4
    24 No. 1 5 3 /4 7 1 /2
    No. 2 5 1 /2 6 1 /2
    No. 3 5 5 1 /2
    For SI: 1 inch = 25.4 mm. NAIL REQUIREMENTS FOR WOOD SHAKES AND WOOD SHINGLES
    SHAKES NAIL TYPE AND MINIMUM LENGTH MINIMUM HEAD SIZE
    MINIMUM SHANK DIAMETER
    18" straight-split 5d box 1 3 /4" 0.19" .080"
    18" and 24" handsplit
    and resawn For SI: 1 inch = 25.4 mm.

    R905.7.6 Valley Flashing

    Roof flashing shall be not less than No. 26 gage [0.019 inches (0.5 mm)] corrosion-resistant sheet metal and shall extend 10 inches (254 mm) from the centerline each way for roofs having slopes less than 12 units vertical in 12 units horizontal (100-percent slope), and 7 inches (178 mm) from the centerline each way for slopes of 12 units vertical in 12 units horizontal (100-percent slope) and greater. Sections of flashing shall have an end lap of not less than 4 inches (102 mm).

    R905.7.7 Label Required

    Each bundle of shingles shall be identified by a label of an approved grading or inspection bureau or agency.

    R905.8 Wood Shakes

    The installation of wood shakes shall comply with the provisions of this section.

    R905.8.1 Deck Requirements

    Wood shakes shall be used only on solid or spaced sheathing. Where spaced sheathing is used, sheathing boards shall be not less than 1-inch by 4-inch (25 mm by 102 mm) nominal dimensions and shall be spaced on centers equal to the weather exposure to coincide with the placement of fasteners. Where 1-inch by 4-inch (25 mm by 102 mm) spaced sheathing is installed at 10 inches (254 mm) on center, additional 1-inch by 4-inch (25 mm by 102 mm) boards shall be installed between the sheathing boards.

    R905.8.1.1 Solid Sheathing Required

    In areas where the average daily temperature in January is 25°F (-4°C) or less, solid sheathing is required on that portion of the roof requiring an ice barrier.

    R905.8.2 Deck Slope

    Wood shakes shall only be used on slopes of three units vertical in 12 units horizontal (25-percent slope) or greater.